OVERALL CHECKING
Note:
The installation guide above covers only the fan coil unit. For installation of outdoor (mini chiller etc) please refer to
the installation guide for such unit.
The installation of fan coil unit may vary according to the type of outdoor unit.
Installation must be done by qualified personnel who is familiar with this type of product.
SERVICE AND MAINTENANCE
! CAUTION
Avoid direct contact of any coil treatment cleaners on plastic part. This may cause plastic part to deform as a
result of chemical reaction.
Service Parts Maintenance Procedures Period
Indoor Air Filter Remove any dust adhered on the filter by using a vacuum cleaner or wash
in lukewarm water (below 40°C) with neutral cleaning detergent.
Rinse well and dry the filter before placing it back onto the unit.
Do not use gasoline, volatile substances or chemical to clean the filter.
1.
2.
3.
At least once every
2 weeks.
More frequently
if necessary.
Indoor Unit Clean any dirt or dust on the grille or panel by wiping it using soft cloth
soaked in lukewarm water (below 40°C) with neutral detergent solution.
Do not use gasoline, volatile substances or chemical to clean the indoor
unit.
1.
2.
At least once every
2 weeks.
More frequently
if necessary.
Ensure that:
The unit has been mounted solidly and rigid in
position.
The piping and connections are leak-proof.
Proper wiring has been installed.
Drainage check
pour some water into the left side of the drain pan (the
drainage is at the right side of the unit).
1)
2)
3)
Test run:
Conduct a test run on the unit after having perform the
water drainage test and the gas leakage test.
Check the following items:
Is the electrical plug inserted firmly into the socket?
Is
there any abnormal sounds from the unit?
Is there any abnormal vibrations on the unit or the
piping?
Is t
he drainage of water smooth?
Confirm that:
The evaporator blower is running and discharge cool
air.
1)
2)
a)
b)
c)
d)
1)
Note is valid for Turkey only: The lifetime of our products is ten (10) years
1 IM-CKEW(DC)-1013(1)DAIKIN-EN.i15 151 IM-CKEW(DC)-1013(1)DAIKIN-EN.i15 15 7/1/14 2:39:07 PM7/1/14 2:39:07 PM
Ваш отзыв будет первым
Задайте вопрос
Ваше имя
E-mail
Вопрос*
Ваш вопрос будет опубликован после проверки
Ваш вопрос опубликован

Смотрите также другие инструкции раздела Daikin