Просмотр инструкции кондиционера Daikin FWG-AT, страница 14

Daikin
1-12
INDICATOR LIGHTS
Event Power LED Timer LED Error Code
1. Room Sensor Open or Short Blink 1 time - Blink E1
2. Pipe Water sensor Open or Short Blink 2 times - Blink E2
3. Pipe Water Temperature poor Blink 3 times - Blink E4
4. Pipe Water Temperature bad/fault
- Blink 1 time Blink E5
5. Water Pump Fault - Blink 2 times Blink E6
6. Hardware Error (tact switch pin Short/M3 or M4
Mode with valveless section)
- Blink 6 times Blink E8
7. Window Open activated* Blink 6 times - -
8. Antifreeze mode activated* Blink 7 times - -
9. Load Shedding activated* Blink 8 times - -
* Only applicable for 4-pipes system
A) MODEL SELECTION
FAN COIL UNIT CONTROLLER BOARD SETTING
(APPLICABLE FOR 4 PIPES UNITS ONLY)
HTR
L
Model M3
Model M4
FAULT DIAGNOSIS
Wireless Controller
When there is infrared remote control operating signal, the signal receiver on indoor unit will make a <beep> for signal
acceptance confirmation.
Wired Controller
If there is any abnormal condition detected, wired controller will blink the error code.
N2
LIVE
N1
HI
MED
LOW
CN_TW
CN_PGRM
CN_WIR
ROOM
CN_STP
C_SENH_SEN
HEAT
VA LV E
CN_DSP
SHED
M4
M3
M2
M1
TFULL A_FRZ W_OPEN UNOCPCO_DRAFT
SLIENT
CVLV
HVLV
WTP
AS
CN_DRY
1 IM-CKEW(DC)-1013(1)DAIKIN-EN.i12 121 IM-CKEW(DC)-1013(1)DAIKIN-EN.i12 12 7/1/14 2:39:07 PM7/1/14 2:39:07 PM