O-CU06-DEC14-1
All specifications are subjected to change by the manufacturer without prior notice. The English te x t is the
original instruction. Other languages are the translations of the original instructions.
6
Low pressure safety (Auto reset)
The low pressure safety switch is recommended to avoid
compressor operat i on at too lower suction pressure and
vacuum conditi on. The low pressure safety cut should never
be set below value as shown in the following table.
* M: Medium temperature; L: Low temperature
The low pressure cut off pressure is the setting of cut in
minus the differential .
3.9 Fan speed controller setting
The fan speed control l er regulates the speed of the
condenser’s f an.
It keeps the condensing pressure at a steady level by
changing the speed of the fan according to the required
condensing press ure.
For model in Series 2 and 4 : Recommended setting for
range setting point er/ range adjusting sc rew as tabl e below:
Medium Temp
Refrigerant
R404A/R407C/R407F/R407A
R134a
Setting (bar) 19
Series 2- 13
Series 4 -10
Low Temp
Refrigerant
R404A/R407A/R407C/R407F
Setting
(bar)
JEHR mo del -19
JEHS model - 13
Cut off: Fan motor stops when the pressure decreases
below the value P
min
.
Note:
F.V.S. = Full Voltage Set Point (pressure setting for
maximum speed)
E.P.B. = Effectiv e Proport i onal Band (6 bar)
P
min
= (F.V.S. 6)
For Series 1 model: Recommended setting for Series 1
model which using pressure switch to on/off fan:
Refrigerant
R404A/
R407A/
R407F
R134a
Setting
(bar)
Cut in
16 10
Setting
(bar)
Differential
7 7
The low pressure cut off pressure is the setting of cut in
minus the differential .
For model in Series 3, the fan speed control l er setti ng as
shown below.
Important No te
There must be no more than 10 compressor starts per
hour. A higher number reduces the
service life of the
compressor. If necessary, use an anti-short-cycle timer in
the control circuit. Minimum a 2 minute runtime after each
start of compressor and a 3
minute idle time after each
stop & start are
recommended. Only during the pump
down cycle may the compressor
run for much shorter
intervals.
Low Pressure side range
a
djusting screw
Clockwise: Decrease cut in
pressure setting
Anticloc
kwise: Increase cut in
pressure setting
Differential adjusting screw
Clockwise: Increase
differential pressu re setting
Anticlockwise:Decrease
differential pressu re setting
Low pressure
side connector
High pressure
side connector
High Pressure side range
adjusting screw
Clockwise: Increase cut off
pressure setting
Anticlockwise: Decrease cut off
pressure setting
Clockwise: Increase pressure
set point
Anticlockwise: Decrease
pressure set point
360° = 1 turn
Approx. 1.5 barg
MEDIUM TEMP MODEL
REFRIG
ERANT: R404A, R407A, R407F
FAN SPEED (RPM)
REFRIGERANT : R134a
FAN SPEED (RPM)
LOW TEMP MO DEL
REFRIGERANT: R404A , R407A
FAN SPEED (RPM)
TEMPERATURE (C°)
TEMPERATURE (C°)
TEMPERATURE (C°)
Manual reset switch