*Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.5m.
Outdoor Unit
LE
Indoor unit
Model
Indoor (ATYN) 20J 25J 35J 50J 60J
Outdoor (ARYN) 20C 25C 35C 50C 60C
Min. Allowable Length (L), m 3
Max. Allowable Length (L), m 12 12 12 20 20
Max. Allowable Elevation (E), m 5 5 5 15 15
Gas Pipe Size, mm/(in) 9.52
(3/8")
9.52
(3/8")
12.70
(1/2")
12.70
(1/2")
15.88
(5/8")
Liquid Pipe Size, mm/(in) 6.35
(1/4")
6.35
(1/4")
6.35
(1/4")
6.35
(1/4")
6.35
(1/4")
Heat Pump Model
If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to
the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective.
Always choose the shortest path and follow the recommendations as tabulated below:
REFRIGERANT PIPING